RTUPS-HSTP3T100KE – (3 Phase) UPS 10-120Kva

$0.00

The Remote Management Card allows administrator to remotely monitor and control CyberPower Smart App UPS, Emergency Power Systems, and Automatic Switches via standard web browsers or the network management system (NMS) on their network. When a power issue occurs, administrator will be notified immediately via e-mail, SNMP traps, and SMS.

Categories: ,

RTUPS-HSTP3T100KE 3-Phase online UPS with in-built battery provides long-lasting power backup for data closets, transportation and infrastructure, and emergency systems. With parallel redundancy capability, the HSTP33 (3-Phase) Series UPS is ideal for critical applications in server rooms, data centers, industrial factories, and power generation plants that require high capacity, high reliability, and extended runtimes.

With integrated IGBT technology and intelligent DSP-based control, the UPS produces less input total harmonic distortion (THDi) and achieves higher power efficiency up to 98% in Economy Mode, making it the most efficient UPS in the industry. Higher operating efficiency equates to lowered BTU heat dissipation and lowered idle power consumption, resulting in an operating expense reduction and a lower carbon footprint.

To improve operating efficiency, the UPS system works in bypass mode under normal conditions, during which the inverter is kept on standby. During power failures, the UPS switches to battery mode and the inverter continuously supplies the critical load to the connected equipment.

Key Benefits

  • For Enterprise Application
  • Input Redundancy Design
  • Compatible with Generator
  • Easy Maintenance
  • Real-time LCD Readout

Typical Applications

  • Data Closets
  • Transportation & Infrastructure
  • Emergency Systems
  • Server Room
  • Data Center
  • Industrial Factory
  • Power Generation

Features

  • Three Phase Tower UPS
  • Online (Double Conversion) UPS Topology
  • Energy Saving Technology
  • Dual Inputs
  • Generator Compatible
  • Pure Sine Wave Output
  • Overload Protection
  • Maintenance Bypass Switch
  • LCD Status Display
  • Emergency Power Off (EPO) Port
  • PowerPanel® Management Software

General

Phase Three Phase Tower UPS
UPS Topology Online Double Conversion
Energy Saving Technology Online ECO Mode Efficiency > 98%
Active PFC Compatibility Yes
Parallel Expansion (Max. Units) 4

Input

Dual Power Inputs Yes
Generator Compatibility Yes
Input Voltage (Vac) Line to Neutral (L-N): 220 ~ 240 Vac
Line to Line (L-L): 380 ~ 415 Vac
Input Voltage Range (Vac) Line to Neutral (L-N): 132 ~ 276 Vac
Line to Line (L-L): 228 ~ 478 Vac
Adjustable Voltage Range (Vac) Line to Neutral (L-N): 220 ~ 250 Vac
Line to Line (L-L): 380 ~ 435 Vac
Input Frequency (Hz) 50 ± 3
60 ± 3
Rated Input Current (A) 138
Input Power Factor 0.99
Input Connector Type Hardwire Terminal Block

Output

Capacity (VA) 100000
Capacity (Watts) 90000
On Battery Waveform Pure Sine Wave
Output Voltage Setting Configurable
Output Frequency Setting Configurable
Power Factor 0.9
ECO Mode Voltage Tolerance ± 10 %
Overload Protection Internal Current Limiting , Circuit Breaker , Fuse
Overload Protection (Line Mode) 105~110% Load for 60 min, 110~125% Load for 10 min, 125~150% Load for 1 min, >150% Load Immediately
Overload Protection (Battery Mode) 105~110% Load for 60 min, 110~125% Load for 10 min, 125~150% Load for 1 min, >150% Load Immediately
Overload Protection (Bypass Mode) 125~130% Load for 10 min, 130~150% Load for 1 min, 150~400% Load for 1 sec, >400% Load Immediately
Crest Factor 3 : 1
Harmonic Distortion (Linear Load) THD<1%
Harmonic Distortion (Non-linear Load) THD<5.5%
Internal Bypass Automatic Bypass , Manual Bypass
Maintenance Bypass Yes
Outlet Type Hardwire Terminal Block x 1
Typical Transfer Time (ms) 0

Battery

Typical Recharge Power (%) 20 % x Power
Recharge Power Setting Configurable
Smart Battery Management (SBM) Yes
User-replaceable No

Surge Protection & Filtering

EMI/RFI Filtration Yes

Management & Communications

LCD Panel Yes
LCD Information Display Operation Type , Power Status , Battery Status , Load Status , Fault & Warning , Other Information , Event & Log
LCD Setting & Control Mode Setting , Input & Output , Battery Setting , Communication , Event & Log , Security Setting , Language
LED Indicators Yes
Serial Port RS232 x 1 + RS485 x 1 + Dry Contact x1
Dry Contact (with Relay) Yes
Emergency Power Off (EPO) Port Yes
Audible Alarms Battery Mode , Low Battery , Overload , Overcharge , Overheat , UPS Fault , Replace Battery
Power Management Software PowerPanel® Business Edition
SNMP / HTTP Remote Monitoring Yes – with optional RMCARD205

Physical

Form Factor Tower
Enclosure Construction Metal
Color Black

Physical Size – Power Module

Dimensions (WxHxD) (mm.) 600 x 1400 x 980
Weight (kg.) 266

Shipping Dimensions

Dimensions (WxHxD) (mm.) 755 x 1600 x 1130
Weight (kg.) 313

Environmental

Operating Temperature (°C) 0 ~ 40
Operating Relative Humidity (Non-condensing) (%) 0 ~ 95
Operating Elevation (feet/meters) ≤1000, Load Derated 1% per 100m from 1000m and 2000m
Storage Temperature (°C) -40 ~ 70
Storage Relative Humidity (Non-condensing) (%) 0 ~ 95
Audible Noise at 1.5M from Surface of Unit (dBA) 58

Certifications